All nonmetallic outlet and switch boxes intended for use in fire-resistant rated assemblies must be specifically investigated for use in such assemblies, and are required to be marked as follows:
• The certification mark located in the base of the box
• Class * hr, where * indicates the hourly rating (i.e. 1 hr or 2 hr)
• F, W, and/or C, where F = Floor, W = Wall, and C = Ceiling
These nonmetallic boxes are Classified for use in certain fire-resistive designs when installed in accordance with the details prescribed for each Classified product.
The information for each Classification includes:
• The model numbers for the Classified products
• A description of the fire-resistant rated assemblies
• The spacing limitations for the boxes
• Installation details